Smart Power Quality Monitoring And Harmonic Reduction In Electrical Distribution Systems Using Intelligent Control Techniques
Keywords:
power quality, harmonic mitigation, shunt active power filter, fuzzy logic control, total harmonic distortion, distribution systemsAbstract
Non-linear loads inject harmonic currents that distort waveforms in distribution systems, and mitigation is most useful when it is triggered by what is measured on the feeder. This paper presents a smart power quality framework in which a per-cycle FFT monitor measures the source-current total harmonic distortion (THD) and enables a shunt active power filter (SAPF) when THD exceeds 5 % for two consecutive cycles. The SAPF combines in-phase current extraction with a sliding mean, hysteresis current control and a DC-link controller, implemented in two versions: a conventional PI controller and an intelligent fuzzy-logic controller. A three-phase 230 V, 50 Hz feeder with a six-pulse rectifier load that steps from 40 A to 60 A is simulated at switching level in Python. Without filtering, the source-current THD is 23.8 %, with 5th, 7th, 11th and 13th harmonics of 18.2, 12.0, 6.4 and 4.9 % of the fundamental. The monitor detects the condition and activates the filter after 40 ms. In steady state, THD falls to 1.51 % with the PI controller and 1.28 % with the fuzzy controller; after the load step it is 4.12 % and 3.88 %. The fuzzy controller gives slightly lower distortion but a larger and slower DC-link transient (731 V peak and 67 ms settling against 707 V and 19 ms for PI), so its advantage is limited. The source is assumed stiff and ideal, the parameters are assumed, and no hardware validation is included.